Derived bases: [ I_base = \fracS_base\sqrt3 V_base, \quad Z_base = \frac(V_base)^2S_base ]
Fault clears at angle ( \delta_c ). System stable if area ( A_1 ) (accelerating) = area ( A_2 ) (decelerating).
[ C = \frac2\pi \epsilon_0\ln(D/r) \ \textF/m ] power system analysis lecture notes ppt
| Concept | Formula | |---------|---------| | Base impedance | ( Z_base = V_base^2 / S_base ) | | Y-bus element | ( Y_ik = -y_ik ) (off-diag) | | Newton-Raphson | ( \beginbmatrix \Delta P \ \Delta Q \endbmatrix = J \beginbmatrix \Delta \delta \ \Delta |V| \endbmatrix ) | | Sym. fault current | ( I_f = V_th / (Z_th+Z_f) ) | | SLG fault | ( I_f = 3V_f / (Z_1+Z_2+Z_0) ) | | Swing equation | ( (2H/\omega_s) d^2\delta/dt^2 = P_m - P_e ) |
[ \textpu value = \frac\textActual value\textBase value ] Derived bases: [ I_base = \fracS_base\sqrt3 V_base, \quad
Generator: 10 MVA, 11 kV, ( X_d'' = 0.12 ) pu. Transformer 10 MVA, 11/132 kV, ( X_t = 0.08 ) pu. Line impedance 20 Ω (on 132 kV). Fault at 132 kV bus. Find ( I_f ) in kA.
[ L = 2\times 10^-7 \ln \left( \fracDr' \right) \ \textH/m ] where ( r' = r \cdot e^-1/4 ) (geometric mean radius, GMR). fault current | ( I_f = V_th /
[ I_f = \fracV_thZ_th + Z_f ] where ( Z_th ) includes generators (using subtransient reactance ( X_d'' )).